电子科技 ›› 2024, Vol. 37 ›› Issue (2): 61-68.doi: 10.16180/j.cnki.issn1007-7820.2024.02.009

• • 上一篇    下一篇

基于RTDS的直驱风机硬件在环实验方法

何朴想,郝正航,陈卓,杨光绕,聂春芳   

  1. 贵州大学 电气工程学院,贵州 贵阳 550025
  • 收稿日期:2022-10-08 出版日期:2024-02-15 发布日期:2024-01-18
  • 作者简介:何朴想(1996-),男,硕士研究生。研究方向:电力系统及其自动化。|郝正航(1972-),男,博士,教授。研究方向:新能源发电与智能电网。
  • 基金资助:
    第二批国家级新工科研究与实践项目(E-NYDQHGC20202227)

Research on Hardware in Loop Experiment Method of Direct Drive Wind Turbines Based on RTDS

HE Puxiang,HAO Zhenghang,CHEN Zhuo,YANG Guangrao,NIE Chunfang   

  1. The Electrical Engineering College,Guizhou University,Guiyang 550025,China
  • Received:2022-10-08 Online:2024-02-15 Published:2024-01-18
  • Supported by:
    The Second Batch of National New Engineering Research and Practice Project(E-NYDQHGC20202227)

摘要:

为实现风电机组硬件在环平台的通用性,文中在环实验平台搭建了通用风电机组硬件,完成了风电机组的优化控制。针对直驱风机在电网电压不平衡或不对称的情况下影响直驱风机正常运行的问题,文中采用基于正序和负序的电流解耦算法消除负序电流以保持恒定的输出功率。通过抑制故障时风电机组的无功功率两倍频波动,使有功和无功基准值均为0,电网无功功率两倍频波动分量的幅值为0,达到消除负序电流使风电机组稳定输出的目的,并在该实验平台进行仿真验证。实验结果表明,风电机组有功功率输出保持不变,显著提高了风电机组并网的适应性,验证了该方法的合理性和有效性。

关键词: 直驱风机, 实时数字仿真器, 不平衡电压, 锁相环, UREP, 通用平台, 硬件在环, 优化控制

Abstract:

In order to realize the generality of wind turbines hardware in the loop platform, a universal wind turbines hardware in the loop experiment platform is built to realize the optimal control of wind turbines. In view of the problem that direct drive wind turbines can affect the normal operation of direct drive wind turbines when the power grid voltage is unbalanced or asymmetrical, this study adopts the algorithm based on the decoupling of positive sequence current and negative sequence current to eliminate the negative sequence current and keep the constant output power. By inhibiting the double frequency fluctuation of the reactive power of the wind turbines when the fault occurs, the reference value of the active power and reactive power is 0, the amplitude of the double frequency fluctuation component of the grid reactive power is 0, and the purpose of eliminating the negative sequence current and making the output of the wind turbines stable is achieved. The simulation verification is carried out on the experimental platform. The experimental results show that the active power output of wind turbines remains unchanged and the grid-connection adaptability of wind turbines is significantly improved, which verifies the rationality and effectiveness of the method.

Key words: direct drive wind turbines, RTDS, unbalance voltage, phase-locked loop, UREP, universal platform, hardware-in-loop, optimal control